Bag house controls for pulse jet dust collectors
Models & Specifications — Previous Page

Technical Data

Factory Default Settings
Lo Pressure Alarm
0.5” water column
Lo Pressure
2” water column
Hi Pressure
4” water column
Hi Pressure Alarm
10” water column
Output Quantity
10
Off Time
15 seconds
On Time
0.05 seconds
Output Configuration
Manual
Units
Inches (metric optional)
Unattainable Lo Pressure
15 cycles
Display Language
English, Spanish or French
Cycle Down
Not selected
Number of Cycles 2 cycles

Inputs
Voltage
105 - 135 VAC, 50/60 Hz

Maximum Ratingsat 135 VAC Input Voltage
Power Consumption 10 VA, without loads
By-pass Switch Open Circuit Voltage
24 VDC
By-pass Switch Short Circuit Current
4.3 mA
Alarm Input Switch Open Circuit Voltage
24 VDC
Alarm Input Switch Short Circuit Current 4.3mA

Outputs
Maximum Solenoid
Output
200VA or Watts at maximum duty cycle
Solenoid Output Voltage
Input Voltage -2.5 VAC at 200 VA Load
Solenoid Output Type
Solid State TRIAC
Solenoid Output Short Circuit Protection
3AG Fast 3A/250 VAC Fuse
Alarm Output Type
1-FORM A Relay Contact
Alarm Output Rating 3 Amp @ 120/240 VAC

Current Sense Monitor
Minimum Solenoid Load
5VA for auto output sense to detect load present
Air Pressure Measurement
Sensor Type
Silicon Piezoresistive Transducer with Dual Inlets
Measurement Range Typically 0.0 to 25.0 inches of water in .1 increments or .00 to 6.23 KPascals in .01 increments

Air Pressure Measurement
Measurement Range
(continued)
Minimum 0.0 to 17.0 inches of water accuracy: 0.0 to 15.0 inches of water (.00 to 3.74 KPascals) +/- 2% of Full Scale at 77 degrees Fahrenheit, (25 degrees Celsius); +/- 6% of Full Scale over temperature and voltage range.

MaximumContinuous Pressure 10 PSI (276.8 inches of water)

Burst Pressure 100 PSI (2768 inches of water)

NOTE: When changing between English and Metric measurements there may be rounding errors; all pressure settings need to be verified after changing units selection.

Timing
Solenoid On Time Range
.05 - .20 seconds
Solenoid Off Time Range
3 - 180 seconds
Timing Accuracyr -2mS, +10mS or +/-1%, whichever is greate
Solenoid On Time Synchronized to the AC Line
CDC Power Cycle Display 120 seconds +/-1 second

Display
Type: 8 character, 16 segment vacuum fluorescent display (VFD)
Characters .25” high; alphanumeric

Current Loop
Type: 4-20 milliamp current loop; current is sourced by this controller; signal represents 0-25 inch differential pressure
Accuracy +/-1% of displayed pressure

Serial Communications
Type: RS-232
Terminal: ANSI or ANSI Terminal Emulation Program
Mode: 9600 Baud, 8-data bits, 1-start bit, 1-stop bit, no parity
Connector Type: 9-pin male HD style
Interface Cable: Null modem serial cable when interfaced to an IBM compatible computer
An ANSI-based Terminal Software Package is Required

Environmental
Operating Temperature -40 to 149 degrees Fahrenheit;
Range
-40 to 65 degrees Celsius
Warm-up Delay
Less than 50 degrees
Temperature Fahrenheit; 10 degrees Celsius

Important Notice to Users: Our timers are capable of use in a wide array of devices and in various applications. Any device or system incorporating a timer should be so designed that, in the event of failure, malfunction or normal wear-out of the timer, the system will become inoperative in a manner which will prevent property damage or bodily injury.
Caution:
1. Do not mount controls in high vibration areas without shock mounts.
2. Do not mount controls in areas of high dust or corrosive atmospheres without a protective enclosure.
3. Do not use a converter or inverter for the power source.
4. Do not mount control in high transient voltage areas without an isolation transformer.
5. Do not leave control box open.
6. Do not allow a local repair shop to repair the controls, as we employ some very sophisticated components that could be
further damaged. For service, call us directly at: 630-775-0707.
Flex-Kleen offers NEMA-4 type enclosures as standard for mounting our controls. These enclosures are made of heavy gauge steel and have a continuous hinge cover. All seams are continuously welded. The finish is gray hammer-tone enamel inside and out, over phosphatized surfaces. Viewport included. Other NEMA Classified enclosures available.
Note: In order to keep abreast of the latest technology, Flex-Kleen reserves the right to change components and/or design of controls without notice.
 
— Previous Page
 
Flex-Kleen Division
45 North Brandon Drive
Glendale Heights, IL 60139
Toll Free: 1-800-621-0734
Phone: 630-775-0707
Fax: 630-295-9019
E-mail: info@flex-kleen.com

Flex-Kleen Canada, Inc.
201 Millway Ave., Suite 28 (Jane & Hwy 7)
Vaughan, Ontario, Canada L4K 5K8
Phone: 905-760-9000
Fax: 905-760-9060
Email: rreinke@met-pro.com

HOME | PROFILE | NEW | BIN VENTS FILTERS | WELDED MODULAR DUST COLLECTORS
HIGH PRESSURE/HIGH VACUUM PULSE JET DUST COLLECTORS
CARTRIDGE DUST COLLECTORS | CYCLONE DUST COLLECTORS | OPTIONS
UPGRADES, REBUILDS & CONVERSIONS | FIELD SERVICES
REPLACEMENT FILTERS & PARTS
| LITERATURE
LOCATE REPS
| REQUEST QUOTE | CONTACT | REP LOG-IN

© 2008 Flex-Kleen Division